Eight special generator sets for a British distribution centre
Distribution centre in the United Kingdom
To supply power in the event of a mains failure in a great distribution centre in th UK
- 2000L fuel tank integrated in the base frame with a drip tray with capacity to collect 110% the capacity of the actual fuel tank.
- 4500 mm special canopy painted in grey (RAL 7012).
- Parallel operation between gensets with Deep Sea 8610 control panel and motorized circuit breaker. Furthermore, through Deep Sea 8660 control panels, the gensets will operate in groups of four in parallel operation with the mains.
- Link box to connect the power cables (3 x 180mm cables per phase).