Genesal Energy, life-saving energy.
In the heart of Lancashire, Genesal Energy has successfully completed the installation of three soundproofed generator sets at a hospital in Blackpool.
We reinforce our commitment to the protection of critical spaces ensuring that patients and healthcare staff can carry out their activities without interruption in the event of a power failure.
Electrical power is the backbone of Hospitals’ daily operations. Without it, medical procedures, diagnostic tests, IT equipment and other essential services would come to stand still. Backup generator sets ensure that, in the event of a grid failure, the hospital can continue its activity without problems.
Genesal Energy installed three generator sets of 330 kVA each, specifically designed to meet the hospital’s needs. The units, insulated not to exceed 75 dB(A) at 1 metre, were manufactured in specially dimensioned canopies and finished with C5M environmentally resistant paint. In addition, they are synchronised with each other by means of a DeepSea DSE8610 control system, which ensures perfect operability between the units.
Each generator has a 650 litre fuel tank and a transfer system that allows continuous fuel supply from an external tank at ground level. Anti-condensation heaters on the alternators and anti-corrosion treatment on the windings have also been added to ensure their operability in all climate conditions.
The careful design of this project not only responds to the high technical standards that a hospital requires, but also to the importance of maintaining a quiet environment for patients and workers.
Our Engineering Solution
Supply of an emergency network with the design, manufacture and commissioning of soundproofed generator sets which guarantee the operation and safety of the centre’s activities at all times.
Features
- 3 x 330kVA Specially oversized soundproofed canopy 75db(A) @ 1m, C5M surface treatment in customised RAL.
- DeepSea DES8610 Control panel for synchronisation between units.
- 650 litres Integrated fuel tanks.
- External fuel filling point with 3 x transfer pumps, solenoid valves, leakage sensors, fuel polishing systems, and connection boxes.
- Anti-condensation heaters on alternator.
- Anti-corrosion treatment on alternator windings, PMG and neutral contactors.
Prime power: 300 kVA
Standby power: 330 kVA
Voltage: 400/230 V
Frequency: 50 HZ
RPM: 1500
Engine: FPT
Alternator: Leroy Somer